Skip to main contentSkip to content

Regulatory guide

NOM-127-SSA1-2021: Permissible Limits for Drinking Water

Mexico’s standard for water for human use and consumption, in force since April 2023
The full table of limits published in the DOF, what changed from NOM-127-SSA1-1994 and how a hotel, condominium or plant with its own water system complies.

NOM:
 
Mexico’s official standards
COFEPRIS:
 
Mexico’s federal health regulator
EMA:
 
Mexico’s laboratory accreditation body

NOM-127 requirements in one minute

E. coli or thermotolerant coliformsFrequency: MonthlyNot detectable in 100 mL
Free chlorine residualFrequency: Daily, in a log0.2 – 1.5 mg/L
TurbidityFrequency: Quarterly (physicochemical)≤ 3.0 NTU
Total hardness (as CaCO₃)Frequency: Quarterly (physicochemical)≤ 500 mg/L

Limits of NOM-127-SSA1-2021. The frequencies are our recommendation for hotels and condominiums: the standard does not set them. See the full parameter table ↓

What is NOM-127-SSA1-2021?

NOM-127-SSA1-2021 is the Mexican Official Standard that sets the permissible limits for the quality of water for human use and consumption, as well as the treatments to make it potable. It is enforced by the Ministry of Health through COFEPRIS.

Main objective

To protect public health by setting the sanitary requirements water must meet to be considered fit for human consumption: free of pathogenic microorganisms and toxic substances, and with acceptable organoleptic characteristics.

Official text of NOM-127-SSA1-2021

Full text published in the Diario Oficial de la Federación (DOF) on May 2, 2022, in force since April 2023.

View in the DOF (in Spanish)

Who does it apply to?

It is mandatory for the bodies responsible for public and private water supply systems. In practice, anyone who operates their own well, cistern or treatment plant must comply:

  • Public water supply systems (municipal utilities)
  • Hotels, restaurants and other lodging facilities
  • Hospitals and health centers
  • Schools and educational institutions
  • Industries that supply water to workers
  • Condominiums and residential developments
  • Any establishment that supplies drinking water

Do you manage a hotel?

Drinking water is one of six water areas at your hotel

Pools, ice, hot water, mechanical room and wastewater discharges: we cover them in one monthly program, with the compliance file ready for COFEPRIS, the Distintivo H and brand audits.

Table of permissible limits of NOM-127-SSA1-2021

Values from the text published in the DOF; in mg/L unless another unit is given

Physical specifications

ParameterUnitPermissible limitNote
TurbidityNTU3.04.0 NTU in the first year; 3.0 since April 2025
pHpH units6.5 – 8.5Permissible range
True colorCU15Previously 20 Pt-Co units

Chemical specifications

ParameterLimit (mg/L)Note
Total cyanides0.07—
Total hardness (as CaCO₃)500—
Fluorides (as F⁻)1.50Phased down to 1.0 (see below)
Ammonia nitrogen (N-NH₃)0.50—
Nitrate nitrogen (N-NO₃⁻)11.00—
Nitrite nitrogen (N-NO₂⁻)0.90—
Total dissolved solids1000—
Sulfates (SO₄²⁻)400—
Methylene blue active substances0.50Detergents

Metals and metalloids

MetalLimit (mg/L)Note
Aluminum0.20—
Arsenic0.025Phased down to 0.010
Barium1.3—
Cadmium0.005Phased down to 0.003
Copper2.00—
Total chromium0.05—
Iron0.30—
Manganese0.15—
Mercury0.006—
Nickel0.07New in 2021
Lead0.01—
Selenium0.04New in 2021

Microbiological specifications

ParameterPermissible limitWhen it applies
E. coli or thermotolerant coliforms< 1.1 MPN/100 mL or not detectable · < 1 CFU/100 mL · absent in 100 mLDepending on the method: MPN, membrane filtration or presence-absence
Giardia lambliaAbsent in 20 LOnly if the source is surface water or influenced by it
Important: E. coli in water indicates recent fecal contamination and is not tolerated in any sample. If it appears, disinfect immediately and resample.

Disinfection residuals

ParameterPermissible limit
Free chlorine residual0.2 – 1.5 mg/L
Free iodine residual0.2 – 1.5 mg/L
Total silver0.05 – 0.1 mg/L

Radioactivity, phytotoxins and byproducts

ParameterPermissible limitNote
Microcystin-LR (phytotoxin)1.0 µg/LOnly with a surface water source
Gross alpha radioactivity0.5 Bq/L—
Gross beta radioactivity1.0 Bq/L—
Bromates10 µg/LDisinfection byproduct
Chlorates and chlorites700 µg/L eachDisinfection byproduct
Formaldehyde900 µg/LDisinfection byproduct

The standard also sets limits per compound for trihalomethanes, haloacetic acids and synthetic organic compounds (benzene, toluene, xylenes and others), in its tables 10, 11 and 14.

Fluorides, arsenic and cadmium: limits phased down

Fluorides go to 1.0 mg/L, arsenic to0.010 mg/L and cadmium to0.003 mg/L, with a phase-in period that depends on the size of the locality:

LocalityPhase-in period after entry into forceNew limit applies from
More than 500,000 inhabitants1 yearApril 2024
50,000 to 499,999 inhabitants3 yearsApril 2026
Fewer than 50,000 inhabitants6 yearsApril 2029

What changed from NOM-127-SSA1-1994

NOM-127-SSA1-2021 supersedes the 2000 amendment to the 1994 standard

ParameterNOM-127-SSA1-1994 (2000 amendment)NOM-127-SSA1-2021
Bacteriological indicatorTotal coliforms and E. coliE. coli or thermotolerant coliforms only; Giardia if the source is surface water
Color20 Pt-Co units15 CU (true color)
Turbidity5 NTU4.0 NTU, and 3.0 since April 2025
Odor and taste“Agreeable”No longer specified
Arsenic0.025 mg/L (since 2005)Phased down to 0.010 mg/L
Fluorides1.50 mg/LPhased down to 1.0 mg/L
Cadmium0.005 mg/LPhased down to 0.003 mg/L
Mercury0.001 mg/L0.006 mg/L
Barium0.70 mg/L1.3 mg/L
Nitrates (as N)10.00 mg/L11.00 mg/L
Nitrites (as N)1.00 mg/L0.90 mg/L
Chlorides, zinc and sodium250, 5.00 and 200 mg/LNo longer listed
New—Nickel, selenium, microcystin-LR, bromates, chlorates, chlorites, formaldehyde and haloacetic acids

What it means for a hotel in Quintana Roo

If your testing was done against the 1994 table, check above all E. coli (reporting total coliforms is no longer enough), turbidity and color. In Cancún, a locality of more than 500,000 inhabitants, the 0.010 mg/L arsenic and 1.0 mg/L fluoride limits have applied since April 2024.

How often to test the water

NOM-127 sets the limits; control of distributed water is governed by NOM-179-SSA1-2020

The standard does not say how often to sample. For a hotel or condominium with its own system, this is what we recommend so you have evidence when the COFEPRIS inspection comes:

What is measuredRecommended frequencyWho measures it
Free chlorine residual and pHDaily, in a logDPD kit or analyzer, by your own staff
E. coli or thermotolerant coliformsMonthlyEMA-accredited laboratory
Physicochemical (turbidity, hardness, TDS, nitrates, common metals)QuarterlyEMA-accredited laboratory
Toxic metals and special parametersWhen the source changes or a result is out of complianceEMA-accredited laboratory

Our services for NOM-127 compliance

Grupo Eytra helps you comply and keep the evidence ready for inspection

Laboratory testing

In EMA-accredited laboratories, with results in 5–7 days and a report for COFEPRIS.

Water treatment

Drinking water treatment systems, automatic chlorination, filtration and UV disinfection.

Monitoring program

Sampling scheduled around your operation, with a history of results for comparison.

Documentation

Reports for COFEPRIS inspections, maintenance logs and evidence of compliance.

Practical guide

How to apply NOM-127 in your operation

What it means for hotels in the Riviera Maya

Hotels in the region face specific challenges in meeting NOM-127:

Well water quality

Most hotels in Quintana Roo draw water from deep wells in the karst aquifer. This water typically has:

  • High hardness: our own tests of untreated water in the Cancún Hotel Zone range from 360 to 492 mg/L as CaCO₃ (8 analyses), which calls for softening or reverse osmosis.
  • High total dissolved solids (TDS), depending on well depth and distance from the sea.
  • Elevated sulfates and chlorides in coastal areas, from saltwater intrusion.

Treatment required

To comply, a typical hotel water treatment train includes:

  1. Prefiltration with multimedia or activated carbon
  2. Softening with ion-exchange resins or antiscalant dosing
  3. Reverse osmosis to reduce TDS and dissolved salts
  4. Disinfection with chlorine, UV or both
  5. Storage in cisterns with a controlled chlorine residual

For drinking water systems, see our water softeners and filtration and chemical treatment pages.

What it means for industry

Industrial plants that use drinking water in their processes (food, pharmaceutical, bottling) must make sure the water meets NOM-127 at the point of use. That means:

  • Continuous monitoring at critical process points
  • Documented records of control parameters
  • Preventive maintenance of treatment systems
  • Staff training in sampling protocols

For industrial plants, non-compliance can mean not only regulatory sanctions but also rejected product, recalls and damage to the brand’s reputation.

Documentation and records

COFEPRIS checks not only water quality but also document traceability. The records every water supply system must keep include:

  • Laboratory test results
  • Operating logs of treatment equipment
  • Chemical dosing records
  • Calibration certificates of measuring instruments
  • Preventive maintenance programs
  • Standard operating procedures (SOPs)

For daily control

NOM-127-SSA1: frequently asked questions

Common questions about drinking water quality in Mexico

What does NOM-127-SSA1-2021 establish?

The permissible limits for the quality of water for human use and consumption: physical (turbidity, pH, color), chemical, metals, microbiological, radioactive, residual and disinfection byproducts. It replaces NOM-127-SSA1-1994 and its 2000 amendment.

When did NOM-127-SSA1-2021 take effect?

It was published in the Diario Oficial de la Federación (DOF), Mexico’s official gazette, on May 2, 2022, and took effect 360 days later, in April 2023. Some limits are phased in: turbidity drops to 3.0 NTU from the second year, and fluorides, arsenic and cadmium drop over 1, 3 or 6 years depending on the size of the locality.

Who must comply with this standard?

It is mandatory for the bodies responsible for public and private water supply systems. A hotel, condominium, hospital or plant that supplies water for drinking or human use from its own well, cistern or treatment plant operates a private system and must comply.

How much chlorine should drinking water have under NOM-127?

Free chlorine residual must be between 0.2 and 1.5 mg/L. Below 0.2, disinfection is not assured; above 1.5, the water is out of compliance and the chlorine taste is noticeable.

What changed from NOM-127-SSA1-1994?

The bacteriological indicator becomes E. coli or thermotolerant coliforms; color (from 20 to 15) and turbidity (from 5 to 3.0 NTU) go down, and arsenic (to 0.010 mg/L), fluorides (to 1.0 mg/L) and cadmium (to 0.003 mg/L) are phased down. Nickel, selenium, Giardia, microcystin-LR and disinfection byproducts are added, and chlorides, zinc and sodium are removed.

What happens if my hotel’s water does not comply?

The health authority can apply the safety measures and sanctions of Mexico’s General Health Law, such as suspension of service or fines. And if a guest falls ill, the legal and reputational risk falls on the hotel. That is why it pays to have recent laboratory results and an up-to-date chlorine log.

How often should I test my property’s water?

NOM-127 sets the limits, not the frequency; control of distributed water is governed by NOM-179-SSA1-2020. For hotels and condominiums, we recommend measuring chlorine and pH daily, E. coli monthly and a physicochemical panel every quarter.

Does Grupo Eytra carry out NOM-127 testing?

Yes. We collect the samples and coordinate the tests NOM-127 requires through EMA-accredited laboratories: microbiological (E. coli), physicochemical and metals. The report supports your COFEPRIS inspection.

Does your hotel comply with NOM-127?

Testing in EMA-accredited laboratories and a compliance program for hotels and resorts in Cancún and the Riviera Maya